INTERNATIONAL METAL
ENGINEERING |
|
|
|
|
|
|
|
|
INDICATING TEMPERATURE
TRANSMITTER |
|
|
|
9008PN |
|
|
|
|
|
|
n |
TYPE J / K THERMOCOUPLE
OR RTD INPUT |
|
|
|
|
|
|
|
|
|
|
|
|
|
n |
PANEL MOUNT 1/8 DIN, HIGH
IMPACT PLASTIC |
|
|
|
|
|
|
|
|
|
|
|
n |
NEMA 4 FRONT PANEL |
|
|
|
|
|
|
|
|
|
n |
4 DIGIT 0.5" LED
DISPLAY |
|
|
|
|
|
|
|
|
|
n |
CHOICE OF DEGREES F OR C |
|
|
|
|
|
|
|
|
n |
ISOLATED 4 TO 20MA OUTPUT |
|
|
|
|
|
n |
3 YEAR WARRANTY |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Introduction |
|
|
|
|
|
Functional Specifications |
|
|
|
IME Model 9008PN is an
isolated indicating transmitter which coverts |
|
Sensor |
|
|
|
|
input from a Type J/K
Thermocouple or Pt100 sensor into a load |
|
|
|
|
|
independent 4-20mA
process signal. A 4 digit bright red LED allows for |
|
Type J/K Thermocouple or Platinum RTD (Switch
Selectable) |
|
|
|
local indication of
Temperature, which is switch selectable to read Degree |
Indication Accuracy |
|
|
|
|
C or F. |
|
|
|
|
|
|
|
0.1% of Calibrated range +/- 1 digit |
|
|
|
|
|
|
|
|
Lead Compensation Error |
|
|
|
|
|
|
|
|
|
|
|
|
<+/-0.05/10W lead
resistance |
|
|
|
|
|
|
|
Stability Over Time |
|
|
|
|
|
|
|
|
|
|
0.1% of calibrated range +/-1 digit over 6 months |
|
|
|
|
Description |
|
|
|
|
|
Temperature Stability |
|
|
|
The Model 9008PN Life
Saver Series Indicating Temperature Transmitter |
|
|
|
|
|
|
accepts the input from a
Pt 100 RTD or Type J or K Thermocouple and |
|
+/-0.01% per
Degree C |
|
|
|
|
|
|
displays temperature in
degrees F or C. The 4 digit display reads from |
|
Burnout Protection |
|
|
|
-999
to 9999 in either unit. All adjustments are made through membrane |
|
|
|
|
|
|
switches provided on the
front panel or by using a IR remote controller. |
|
Upscale |
|
|
|
|
|
|
|
The unit operates off a
24V DC power supply commonly available in |
|
Supply Voltage |
|
|
|
most Control Rooms.
Alternately the unit can be also supplied to work |
|
|
|
|
|
|
off either a 110V AC 60Hz
or 230V AC 50Hz power mains. An isolated |
|
18~28V DC |
|
|
|
|
|
|
|
4 to 20 mA signal is
provided that can be used for indicating or control |
|
Supply and Load Effect |
|
|
|
purpose. |
|
|
|
|
|
|
|
|
<0.03% of span for full change |
|
|
|
|
|
|
Operating Temperature |
|
|
|
|
|
|
|
|
|
|
-50~75oC |
|
|
|
|
|
|
|
|
Weight |
|
|
|
|
|
|
|
|
|
0.18Kg (0.4Lb) |
|
|
|
|
|
|
|
Material of Construction |
|
|
|
Ordering Information |
|
|
|
|
|
|
|
| |
Model |
Description |
|
|
|
|
High Impact Plastic |
|
|
|
|
|
| |
9008PN |
Panel
Mounted Indicating Temperature Transmitter |
|
|
|
|
| |
|
|
with LED Display |
|
|
|
|
|
|
|
| |
|
|
Code |
Power Supply |
|
|
|
|
|
|
| |
|
|
01 |
110V AC +/-10%, 60Hz |
|
|
|
|
|
|
|
| |
|
|
02 |
220V AC +/-10%, 50Hz |
|
|
| |
|
|
03 |
18~28V DC |
|
|
|
|
|
9008PN |
03 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
International Metal
Engineering Pte Ltd |
http://www.intmet.com |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|